Chongqing Yueda Electric Equipment Co., Ltd.

2012 New 96*96MM Digital Panel Meter

2012 New 96*96MM Digital Panel Meter
Product Detailed

1.Measurement of currrent, voltage, active power, power factor.
2.Real time System.
3.With the RS485 Modbus RTUcommunication

Specification Model 

Model  No.

Product Name        

YD4I-9D4

Three-phase AC ammeter (communication/transfer)                                                               

YD4I-9X4

Three-phase AC ammeter

YD4I-9X1

Single-phase AC ammeter

YD5I-9X1

Single-phase DC ammeter

YD4I-9D1

Single-phase AC ammeter (communication/transfer)

YD5I-9D1

Single-phase DC ammeter (communication/transfer)

YD4U-9X4

Three-phase AC voltmeter

YD4U-9D4

Three-phase AC voltmeter (communication/transfer)

YD4U-9X1

Single-phase AC voltmeter

YD5U-9X1

Single-phase DC voltmeter

YD4U-9D1

Single-phase AC voltmeter (communication/transfer)                                                              

YD5U-9D1

Single-phase DC voltmeter (communication/transfer)

 

 Technical Parameter

Performance

Parameter

 
 
 
 
 
 
 
 
 
Input voltage display

Network

3 phase 3 line,3 phase 4 line

 
 
 
Voltage
 
 

Rated voltage

AC100V,400V(please note when purchase)

Overload

Measurement:1.2 times  instantaneous:2 times/10S

Power consumption

<1VA (each phase)

Impedance

>200kΩ

Accuracy

Class 0.5

 
 
 
Current

Rated current

AC1A, 5A(please note when purchase)

Over load

Continuous:1.2 times  instantaneous:10 times/10S

Power consumption

<0.4VA (each phase)

Impedance

<200KΩ

Accuracy

Class 0.5

Frequency

40~60Hz, accuracy 0.2 class

Function

Active power, Reactive power, Apparent power, Accuracy: 0.5 class

Electric energy

Four quadrant measurement, active power
accuracy rate0.5 class, reactive power accuracy rate
1 class

Display

Programmable, switching, LCD/LED display  

Power Supply

Operation range

AC/DC  80~270V

Power consumption

≤5VA

Output

Digital interface

RS-485,MODBUS-RTU

Pulse output

Two power pulse output, photo-couple relay

Environment

Working environment

-10~55ºC

Store environment

-20~75ºC

Safety

Voltage withstand

Input and power>AC 2kV, input and output>AC 2kV

Insulation

Input, output, power supply to machine hull >5MΩ

 

Size (Unit: mm)

 

  

 